Please read this information thoroughly and become familiar with the capabilities and
use of your appliance before attempting to operate or maintain this unit. Keep this
literature where you have easy access to it in the future. If a problem occurs, check the
instructions and follow recommendations given. If these suggestions don’t eliminate
your problem, call your servicing contractor.
The Installation Instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local codes require licensed
installation/service personnel for this type of equipment. Please read all instructions
carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
OUTDOOR SPLIT SYSTEM AIR CONDITIONER FOR MANUFACTURED HOUSING
USER’S MANUAL / INSTALLATION INSTRUCTIONS
NS6QD SERIES - WITH QUICK CONNECT COUPLINGS 13 SEER
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - IMPORTANT

Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain t

Page 2 - INSTALLER INFORMATION

10FIGURES & TABLESFigure 4. Unit DimensionsModel NumberNS6QD-Height -H- Width -W- Depth -D-024 27" 22 3/4" 22 3/4"030 27" 22 3

Page 3 - WARNING:

11Table 4. Electrical Specifi cations & Physical DataModel No. NS6QD 24K 30K 36K 42K 48K 60KElectricalDataVolts-Cycles-Phase 208/230-60-1Total Amps

Page 4 - CAUTION:

12Figure 5. NS6QD Wiring Diagram (2 - 2.5 Ton Units)7110050WIRING DIAGRAMNOTES:FIELD WIRINGLEGEND:LOW VOLTAGEHIGH VOLTAGECRANKCASEHEATER(OPTIONAL)312S

Page 5 - AIR CONDITIONER INSTALLATION

13Figure 6. NS6QD Wiring Diagram (3 Ton Units)

Page 6

14L1L2T1T2CompressorContacts1. Disconnect all power before servicing.2. For supply connections use copper conductors only.3. Not suitable on system

Page 7

15NS6QD CHARGING CHARTS - COOLING ONLYApplication Notes on the Use of Charging Charts• This equipment’s cooling system contains refrigerant under hig

Page 8

16Figure 8. Charging Chart for 2 Ton Units25027530032535037540042545047550052555057560062575 80 85 90 95 100 105 110 115 120 125 130 135Liquid Pressur

Page 9

1725027530032535037540042545047550052555057560075 80 85 90 95 100 105 110 115 120 125 130 135Liquid Pressure (psig)NS6QD-036K TXV Charging ChartRemov

Page 10 - DO NOT OBSTRUCT TOP OF UNIT

1825027530032535037540042545047550052555057560075 80 85 90 95 100 105 110 115 120 125 130 135Liquid Pressure (psig)NS6QD-048K TXV Charging ChartLiqui

Page 12 - WIRING DIAGRAM

2Important Safety Information ...4Air Conditioner Installation ...5 General Infor

Page 13

INSTALLATION / PERFORMANCE CHECK LISTREFRIGERATION SYSTEM:Was unit given 24 hr warm up period for crankcase heaters?YES NOStage-1 Liquid Pressure (hig

Page 14 - High Voltage

3IMPORTANT SAFETY INFORMATIONSafety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not b

Page 15

4INSTALLER INFORMATIONIMPORTANT SAFETY INFORMATIONINSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety

Page 16 - NS6QD-024K TXV Charging Chart

5AIR CONDITIONER INSTALLATIONGeneral InformationThe NS6QD series air conditioner is designed only for outdoor rooftop or ground level installations. T

Page 17 - NS6QD-036K TXV Charging Chart

6Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit CAUTION:This system uses R-410A refrigerant with POE oil. When servicing, cover o

Page 18 - SEE NOTE

7COPPER WIRE SIZE — AWG(1% Voltage Drop)Supply Wire Length-FeetSupply CircuitAmpacity200 150 100 506 8 10 14 1546812 2046810 2544610 303468 353468 402

Page 19

8START UP & ADJUSTMENTSPre-Start Check List Verify the indoor unit is level and allows proper condensate drainage. Verify the outdoor coil and

Page 20 - ¢709217.¤

9• If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3, there is too little charge in the sy